| SPECIFICATIONS |
| MODEL |
6315A |
6330A |
6360A |
6390A |
63120A |
63150A |
63180A |
| INPUT |
| Phase |
3ø |
| Voltage |
220/380Vac±10% |
| Frequency |
47-63Hz |
| Max. Current (approx) |
40A |
75A |
150A |
230A |
300A |
|
|
| Power Factor |
|
0.8 |
| OUTPUT |
| Max. Power |
Single-Phase |
5KVA |
10KVA |
20KVA |
30KVA |
40KVA |
50KVA |
60KVA |
| Total Power |
15KVA |
30KVA |
60KVA |
90KVA |
120KVA |
150KVA |
180KVA |
Max. Current (r.m.s)
, Single-Phase*1 |
0-150V |
42.0A |
84.0A |
168.0A |
252.0A |
336.0A |
420.0A |
504.0A |
| 0-300V |
21.0A |
42.0A |
84.0A |
126.0A |
168.0A |
210.0A |
252.0A |
Max. Current (r.m.s), Single-Phase
(Option 0-600V)*2 |
0-300V |
21.0A |
42.0A |
84.0A |
126.0A |
168.0A |
210.0A |
252.0A |
| 0-600V |
10.5A |
21.0A |
42.0A |
63.0A |
84.0A |
105.0A |
63.0A |
| Phase |
3ø/4W |
| Total Harmonic Distortion (T.H.D) |
< 1% at 360~440Hz or 760~840Hz (Option) at Resistive Load |
| Crest Factor |
≥3 |
| Line Regulation |
± 0.1V |
| Load Regulation |
L - N : ± (0.5% of output +0.5V) / L - L : ± (1% of output +1V) at Resistive Load |
| Deviation of phase angle |
120° ≤ ±1° at Load Balance, 120° ≤ ±2.5° at 100% Load Unblance |
| Response Time |
< 2 msec |
| SETTINGS |
| Voltage |
Range |
0-150V/0-300V Selectable or 0-300V/0-600V Selectable(Option 0-600V) |
| Resolution |
0.1V |
| Accuracy |
±(1% of setting + 2counts) |
| Frequency |
Range |
360-440Hz or 760~840(Option) Full Range Adjust |
| Resolution |
0.1Hz |
| Accuracy |
±0.02% of setting |
| MEASUREMENT |
| Voltage |
L - N Range |
0.0-300.0V / 0.0-600.0V(Option 0-600V) |
| L - L Range |
0.0-520.0V / 0.0-1040V(Option 0-600V) |
| Resolution |
0.1V / 0.2V |
| Accuracy |
± (1% of reading + 2counts) |
| Frequency |
Range |
360.0-440.0Hz; 760.0~840.0Hz (Option) |
| Resolution |
0.1Hz |
| Accuracy |
±0.1Hz |
| Current (r.m.s) |
Range |
L |
0.00-35.00A |
0.0-350.0A |
| H |
30.0-350.0A |
300-504A |
| Resolution |
L |
0.01A |
0.1A |
| H |
0.1A |
1A |
| Accuracy |
L |
± (1% of reading +2counts) |
| H |
± (1% of reading +1count) |
Current (r.m.s)
(Option 0-600V) |
Range |
L |
0.00-35.00A |
| H |
30.0-350.0A |
| Resolution |
L |
0.01A |
| H |
0.1A |
| Accuracy |
L |
± (1% of reading +2counts) |
| H |
± (1% of reading +1count) |
| Power |
Range |
L |
0.000-3.500W |
0.00-35.00KW |
| H |
3.00-40.00W |
30.0-60.0KW |
| Resolution |
L |
0.001W |
0.01KW |
| H |
0.01W |
0.1KW |
| Accuracy |
L |
± (1.5% of reading +5counts) |
| H |
± (1.5% of reading +1count) |
| Power Factor |
Range |
0.000-1.000 |
| Resolution |
0.001 |
| Accuracy |
W / V x A , Calculated and displayed to three significant digits |
| GENERAL |
| PLC Remote |
I/P:ON/OFF, P1, P2, P3, O/P:Processing |
| Memory |
8 Memoies, 5steps per memory for Voltage, Frequency, Test Time, Delay time and Current, Power, Power Factor Hi, Lo Limit setting. |
| Timer |
0=Continuous, 1-9999 (Unit: sec, minute, hour selectable) |
| Auto Loop Cycle |
0=Continuous, OFF=Loop Once, 2~9999 (Unit:×1, ×10, ×100) |
| Auto Voltage Adjust |
Enable it for improve voltage regulation within ±0.1V |
| Efficiency |
≧85%(at Full Load ) |
| Protection |
Over Load , Short Circuit , Over Temperature |
| Calibration |
Front Panel Calibration |
| Interface (Option) |
GPIB/RS232 |
| Operation Environment |
0-40℃/20-80%RH |
| Dimension, mm |
W |
430 |
600 |
800 |
1200 |
1200 |
1600 |
1600 |
| H |
732 |
842 |
1242 |
1557 |
1557 |
1800 |
1800 |
| D |
650 |
900 |
900 |
900 |
900 |
1100 |
1100 |
| Net Weight |
207Kg |
366Kg |
487Kg |
820Kg |
1300Kg |
1800Kg |
2100Kg |
| *1 At working voltage 120/240V |
product specifications are subject to change without notice. |
| *2 At working voltage 240V/480V |
|